Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_G0422

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:21 BD time
100%Form Completion 15/15Checklist OK 1Open Snags 1Total Snags 4Photos Attached

Site & Handover Details

Site CodeSYL_G0422ZoneSylhet
HOTO Date2026-09-06DistrictSunamganj
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd. Anwar HossainTakeover PersonIsmail Hossain
Handover Phone01734713807Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGFT
BTS TypeOutdoor
Shared with OperatorYesShared Operator NameGrameen Phone

Generator Information

DG BrandFG WilsonGenset Asset No.N/A
Capacity (KVA)22TypeCan
Fuel Tank Capacity2000Present RH142
Fuel (no water)277 LFuel (total)369 L
Water Amount90 LFuel Amount (word)Three Hundred Sixty Nine Liters
DG Site TypeRemoteDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033XHBK0641
Battery AH100Engine SerialHP35203U935011S
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)45
Frequency (Hz)49.7Phase3 Phase
Output400Engine BrandPerkings
Voltage L1-L2401Voltage L2-L3401
Voltage L3-L1400Voltage L1-N231
Voltage L2-N231Voltage L3-N230
Current Line 115Current Line 215
Current Line 315N-G2.4
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (1)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-064 DG DG - Other No servicing date found. Faulty Open

Deficiencies & Safety Remarks

DG Major DeficienciesThere is another dg canopy at this site.
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Anwar Hossain
Handed Over By · Dhaly Infratech
01734713807
Date:  
Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (4)

Full-size reference photos for SYL_G0422, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (1)

Photo 4 β€” S-064 β€” No servicing date found.

Download / Print PDFEdit Before Printing