Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0087

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:21 BD time
100%Form Completion 15/15Checklist OK 0Open Snags 0Total Snags 3Photos Attached

Site & Handover Details

Site CodeSYL_X0087ZoneSylhet
HOTO Date2026-09-04DistrictSunamganj
Handover OrgDhaly Infratech LtdTakeover OrgAlliance Computers Limited
Handover PersonMd. AnwerTakeover PersonMd. Ismail hossain
Handover Phone01734713807Takeover Phone01847426758
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGFT
BTS TypeOutdoor
Shared with OperatorNoShared Operator NameN/A

Generator Information

DG BrandTempestGenset Asset No.2001001IBAL
Capacity (KVA)20TypeCan
Fuel Tank Capacity2000Present RH446.4
Fuel (no water)212 LFuel (total)212 L
Water Amount— LFuel Amount (word)Two Hundred Twelve Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialPO33WLDB0008
Battery AH100Engine SerialGV51790U884143B
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-08-23
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)45
Frequency (Hz)50.1Phase3 Phase
Output400Engine BrandPerkings
Voltage L1-L2400Voltage L2-L3400
Voltage L3-L1399Voltage L1-N230
Voltage L2-N229Voltage L3-N230
Current Line 115Current Line 215
Current Line 315N-G2.7
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Anwer
Handed Over By · Dhaly Infratech Ltd
01734713807
Date:  
Md. Ismail hossain
Taken Over By · Alliance Computers Limited
01847426758
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (3)

Full-size reference photos for SYL_X0087, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Download / Print PDFEdit Before Printing