Banglalink Alliance Computers Limited

Site HOTO Report β€” DHK_X5181

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:23 BD time
73%Form Completion 15/15Checklist OK 0Open Snags 0Total Snags 8Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type, BTS Type, Site Sharing.

Site & Handover Details

Site CodeDHK_X5181ZoneSylhet
HOTO Date2026-09-03DistrictNarsingdi
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd MahabubTakeover PersonMir Hossain
Handover Phone01615220637Takeover Phone01715163312
Inspected BySojib HossanSecurity GuardNo
Access Key Handed OverSite TypeNot Filled
BTS TypeNot Filled
Shared with OperatorNot FilledShared Operator Name

Generator Information

DG BrandPramacGenset Asset No.
Capacity (KVA)22Type
Fuel Tank Capacity200Present RH
Fuel (no water)365 LFuel (total)379 L
Water Amount14 LFuel Amount (word)Three Hundred Seventy Nine Liters
DG Site TypeDG Locked After FuelingYes
DG Present StatusOK Genset ON Alarm
Battery BrandBattery Serial
Battery AHEngine Serial
ATS BrandATS ModeAuto
RH Meter TypeLast Service Date
Key TypeLocal KeyKey Status β€” BTS
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DG1Faulty/Disconnected Tanks1

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesPhase3 Phase
Voltage L1-N220Voltage L2-N225
Voltage L3-N229Current Line 1-2
N-G-2Engine BrandPramic
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major Deficiencies1,DG Air Filter Box Lock Missing, 2,Ari Filter Missing 3,Radiator Muntin Broken 4,Out Door BTS Room Light Faulty
Safety Remarks1,Fire Extinguisher Missing
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge

Additional

Additional

Additional

Additional

Additional
Md Mahabub
Handed Over By · Dhaly Infratech
01615220637
Date:  
Mir Hossain
Taken Over By · Alliance Computers Limited
01715163312
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (8)

Full-size reference photos for DHK_X5181, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Additional Photos (5)

Photo 4 β€” Site Context 1
Photo 5 β€” Site Context 2
Photo 6 β€” Site Context 3
Photo 7 β€” Site Context 4
Photo 8 β€” Site Context 5

Download / Print PDFEdit Before Printing