Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0091

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:21 BD time
91%Form Completion 14/16Checklist OK 4Open Snags 4Total Snags 7Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type.

Site & Handover Details

Site CodeSYL_X0091ZoneSylhet
HOTO Date2026-09-03DistrictSunamganj
Handover OrgDhaly Infratech LtdTakeover OrgAlliance Computers Limited
Handover PersonMd. AnwarTakeover PersonMd. Ismail Hossain
Handover Phone01734713807Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeNot Filled
BTS TypeIndoor
Shared with OperatorNoShared Operator NameN/A

Generator Information

DG BrandTempestGenset Asset No.N/A
Capacity (KVA)20TypeCan
Fuel Tank Capacity2000Present RH4980.27
Fuel (no water)118 LFuel (total)157 L
Water Amount39 LFuel Amount (word)One Hundred Fifty Seven Liters
DG Site TypeRemoteDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033XFDF0162
Battery AH100Engine SerialGN66044U
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-06-22
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)25
Frequency (Hz)50.2Phase3 Phase
Output388Engine BrandParkings
Voltage L1-L2388Voltage L2-L3388
Voltage L3-L1388Voltage L1-N224
Voltage L2-N224Voltage L3-N224
Current Line 17Current Line 28
Current Line 37N-G4.35
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionNOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)NOKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OKAVR StatusOK

Snags Found (4)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-043 DG DG - Other DG controller display not visible Faulty Open
S-044 DG DG - Other The radiator is full of dust Faulty Open
S-045 DG DG - Other Lube oil level is low Faulty Open
S-046 General Other/Uncategorized (unspecified) Faulty The tin sheets on the site's roof are damaged, and the brickwork on one side has collapsed; the wall needs to be repaired. Open

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Anwar
Handed Over By · Dhaly Infratech Ltd
01734713807
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (7)

Full-size reference photos for SYL_X0091, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (4)

Photo 4 β€” S-043 β€” DG controller display not visible
Photo 5 β€” S-044 β€” The radiator is full of dust
Photo 6 β€” S-045 β€” Lube oil level is low
Photo 7 β€” S-046 β€” (unspecified)