Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0162

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:23 BD time
73%Form Completion 15/15Checklist OK 0Open Snags 0Total Snags 3Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type, BTS Type, Site Sharing.

Site & Handover Details

Site CodeSYL_X0162ZoneSylhet
HOTO Date2026-08-30DistrictSylhet
Handover OrgDhali Infratech LtdTakeover OrgAlliance Computers Limited
Handover PersonMd. Bulbul AhomedTakeover PersonMd. Ismail hossain
Handover Phone01406394565Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeNot Filled
BTS TypeNot Filled
Shared with OperatorNot FilledShared Operator Name

Generator Information

DG BrandFg wilsonGenset Asset No.20060052IRA
Capacity (KVA)22TypeCan
Fuel Tank Capacity2000Present RH105.7
Fuel (no water)223 LFuel (total)223 L
Water Amount00 LFuel Amount (word)Two Hundred Twenty Three Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033wdcd0250
Battery AH100Engine SerialGv51792R
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-08-22
Key TypeKey Status β€” BTSLocal
Key Status β€” DG RoomOpen space
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DG00Faulty/Disconnected Tanks00

Connected Generator Checklist & Readings

ItemValueItemValue
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major Deficiencies1) Dg fan belt not ok 2) Lube oil sensor & Temp sensor disconnected.
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Bulbul Ahomed
Handed Over By · Dhali Infratech Ltd
01406394565
Date:  
Md. Ismail hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (3)

Full-size reference photos for SYL_X0162, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Download / Print PDFEdit Before Printing