![]() |
![]() |
| 73%Form Completion | 15/15Checklist OK | 0Open Snags | 0Total Snags | 3Photos Attached |
| Site Code | SYL_X0162 | Zone | Sylhet |
|---|---|---|---|
| HOTO Date | 2026-08-30 | District | Sylhet |
| Handover Org | Dhali Infratech Ltd | Takeover Org | Alliance Computers Limited |
| Handover Person | Md. Bulbul Ahomed | Takeover Person | Md. Ismail hossain |
| Handover Phone | 01406394565 | Takeover Phone | 01847426858 |
| Inspected By | Ismail Siraji | Security Guard | Yes |
| Access Key Handed Over | Yes | Site Type | Not Filled |
| BTS Type | Not Filled | ||
| Shared with Operator | Not Filled | Shared Operator Name | — |
| DG Brand | Fg wilson | Genset Asset No. | 20060052IRA |
|---|---|---|---|
| Capacity (KVA) | 22 | Type | Can |
| Fuel Tank Capacity | 2000 | Present RH | 105.7 |
| Fuel (no water) | 223 L | Fuel (total) | 223 L |
| Water Amount | 00 L | Fuel Amount (word) | Two Hundred Twenty Three Liters |
| DG Site Type | Standard | DG Locked After Fueling | Yes |
| DG Present Status | OK | Genset ON Alarm | OK |
| Battery Brand | Hamko | Battery Serial | P033wdcd0250 |
| Battery AH | 100 | Engine Serial | Gv51792R |
| ATS Brand | Local | ATS Mode | Auto |
| RH Meter Type | Digital from controller | Last Service Date | 2026-08-22 |
| Key Type | — | Key Status β BTS | Local |
| Key Status β DG Room | Open space | ||
| Active DG | 1 | Connected Fuel Tanks | 1 |
| Faulty/Disconnected DG | 00 | Faulty/Disconnected Tanks | 00 |
| Item | Value | Item | Value |
|---|---|---|---|
| Controller Status | OK | Black Smoke Status | OK |
| DG Battery Charger | OK | ATS Physical & Functional Status | OK |
| DG Automation (VDTC/RVDTC/Rectifier) per BL Standard | OK | Fuel Preserved at Safe & Appropriate Location | OK |
| Exhaust Fan / Ventilation Sufficient When Running | OK | Sufficient Water in Radiator & Battery | OK |
| DG Radiator Condition | OK | DG Battery Condition | OK |
| DG Runs in Both Auto & Manual Mode | OK | GENSET ON Alarm Functioning Properly | OK |
| Lub Oil Status (Level & Colour) | OK | DG RH Meter Working Properly | OK |
| No Parts Missing (if missing, note in snags below) | OK |
No snags logged for this visit.
| DG Major Deficiencies | 1) Dg fan belt not ok 2) Lube oil sensor & Temp sensor disconnected. | ||
|---|---|---|---|
| Safety Remarks | — | ||
| General Remarks | — | ||
![]() Site / Nameplate |
![]() DG RH / Meter |
![]() Fuel Gauge |
|
Md. Bulbul Ahomed
Handed Over By · Dhali Infratech Ltd
01406394565
Date:
|
Md. Ismail hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:
|
BL Concern · Name / Signature
Date:
|
Photo 1 β Site / Nameplate
|
Photo 2 β DG RH / Meter
|
Photo 3 β Fuel Gauge
|