Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0543

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:23 BD time
100%Form Completion 15/15Checklist OK 1Open Snags 1Total Snags 4Photos Attached

Site & Handover Details

Site CodeSYL_X0543ZoneSylhet
HOTO Date2026-09-02DistrictSunamganj
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd. Eidris AliTakeover PersonMd. Ismail Hossain
Handover Phone01750537433Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGFT
BTS TypeOutdoor
Shared with OperatorNoShared Operator NameN/A

Generator Information

DG BrandTempestGenset Asset No.10020016174084
Capacity (KVA)20TypeCan
Fuel Tank Capacity2000Present RH11629.41
Fuel (no water)171 LFuel (total)297 L
Water Amount171 LFuel Amount (word)Two Hundred Ninety Seven Liters
DG Site TypeRemoteDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033XFOF0145
Battery AH100Engine SerialGN65732U984108T
ATS BrandTempestATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-06-27
Key TypeLocal KeyKey Status β€” BTSLocal Key
Key Status β€” DG RoomOpen
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)30
Frequency (Hz)50.8Phase3 Phase
Output380Engine BrandParkings
Voltage L1-L2382Voltage L2-L3382
Voltage L3-L1380Voltage L1-N221
Voltage L2-N221Voltage L3-N222
Current Line 110Current Line 210
Current Line 39N-G0.005
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (1)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-019 DG DG - Battery/Starter Dg Controller display not visible Faulty Open

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Eidris Ali
Handed Over By · Dhaly Infratech
01750537433
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (4)

Full-size reference photos for SYL_X0543, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (1)

Photo 4 β€” S-019 β€” Dg Controller display not visible

Download / Print PDFEdit Before Printing