Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0073

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:21 BD time
73%Form Completion 13/15Checklist OK 0Open Snags 0Total Snags 3Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type, BTS Type, Site Sharing.

Site & Handover Details

Site CodeSYL_X0073ZoneSylhet
HOTO Date2026-08-30DistrictSylhet
Handover OrgDhali Infratech LtdTakeover OrgAlliance Computers Limited
Handover PersonMd.Bulbul AhomedTakeover PersonMd. Ismail Hossain
Handover Phone01406394565Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeNot Filled
BTS TypeNot Filled
Shared with OperatorNot FilledShared Operator Name

Generator Information

DG BrandFg wilsonGenset Asset No.000
Capacity (KVA)22TypeCan
Fuel Tank Capacity2000Present RH42.2
Fuel (no water)14 LFuel (total)14 L
Water Amount00 LFuel Amount (word)Fourtin
DG Site TypeStandardDG Locked After Fueling
DG Present StatusNOK Genset ON AlarmOK
Battery BrandHamko 100AhBattery SerialP8199420039
Battery AH100Engine Serial35212u9527765
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date
Key TypeKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks00
Faulty/Disconnected DG00Faulty/Disconnected Tanks1

Connected Generator Checklist & Readings

ItemValueItemValue
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationNOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionNOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major Deficiencies1.DG Battery faulty. 2.DG Battery cable aluminium need to change. 3.Hose pipe leakage. 4.Hi temperature sensor broken. 5.DG Dynamo faulty. 6.Silencer pipe leakage. 7.DG Room gate broken. 8.DG canopy lock faulty 9.1 Phase missing 10.Fuel thief aria need to proper protection. 11.1 pcs Transformer Faulty. 12.Last servicing date not found.
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md.Bulbul Ahomed
Handed Over By · Dhali Infratech Ltd
01406394565
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (3)

Full-size reference photos for SYL_X0073, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Download / Print PDFEdit Before Printing