Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0611

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:21 BD time
100%Form Completion 15/15Checklist OK 0Open Snags 0Total Snags 3Photos Attached

Site & Handover Details

Site CodeSYL_X0611ZoneSylhet
HOTO Date2026-09-02DistrictSunamganj
Handover OrgDhaly Infratech LtdTakeover OrgAlliance Computers Limited
Handover PersonMd. Eidris AliTakeover PersonMd. Ismail Hossain
Handover Phone01750537433Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGFT
BTS TypeOutdoor
Shared with OperatorNoShared Operator NameN/A

Generator Information

DG BrandFG WilsonGenset Asset No.1003001QKE2
Capacity (KVA)30TypeCan
Fuel Tank Capacity850Present RH303.2
Fuel (no water)66 LFuel (total)122 L
Water Amount56 LFuel Amount (word)One Hundred Twenty Two Liters
DG Site TypeRemoteDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033WIDE0636
Battery AH100Engine SerialDJ32015*S009835C
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-03-22
Key TypeLocal KeyKey Status β€” BTSOpen
Key Status β€” DG RoomOpen
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)33
Frequency (Hz)50.8Phase3 Phase
Output418Engine BrandParkings
Voltage L1-L2415Voltage L2-L3416
Voltage L3-L1415Voltage L1-N238
Voltage L2-N237Voltage L3-N237
Current Line 111Current Line 211
Current Line 311N-G1.32
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Eidris Ali
Handed Over By · Dhaly Infratech Ltd
01750537433
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (3)

Full-size reference photos for SYL_X0611, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Download / Print PDFEdit Before Printing