Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0086

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 20:21 BD time
100%Form Completion 14/15Checklist OK 2Open Snags 2Total Snags 5Photos Attached

Site & Handover Details

Site CodeSYL_X0086ZoneSylhet
HOTO Date2026-09-02DistrictSunamganj
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd. Eidris AliTakeover PersonMd. Ismail Hossain
Handover Phone01750537433Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGFT
BTS TypeOutdoor
Shared with OperatorYesShared Operator NameRobi

Generator Information

DG BrandFG WilsonGenset Asset No.N/A
Capacity (KVA)22TypeCan
Fuel Tank Capacity850Present RH341.5
Fuel (no water)163 LFuel (total)179 L
Water Amount16 LFuel Amount (word)One Hundred Seventy Nine Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandLucasBattery Serial3AI5VY12787359
Battery AH100Engine SerialHP51109V983311P
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-07-31
Key TypeLocal KeyKey Status β€” BTS00
Key Status β€” DG RoomOpen
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)42
Frequency (Hz)48.8Phase3 Phase
Output401Engine BrandParkingd
Voltage L1-L2401Voltage L2-L3402
Voltage L3-L1402Voltage L1-N230
Voltage L2-N231Voltage L3-N231
Current Line 114Current Line 214
Current Line 314N-G1.86
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionNOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (2)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-017 DG DG - Other DG fan bet losse Faulty Open
S-018 DG DG - Other Radiator s blocked with dust. Faulty Open

Deficiencies & Safety Remarks

DG Major Deficiencies1) Fan belt loose 2) Rediotor not ciling
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Eidris Ali
Handed Over By · Dhaly Infratech
01750537433
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (5)

Full-size reference photos for SYL_X0086, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (2)

Photo 4 β€” S-017 β€” DG fan bet losse
Photo 5 β€” S-018 β€” Radiator s blocked with dust.

Download / Print PDFEdit Before Printing