Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0257

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 25-Oct-2026 20:30 BD time
73%Form Completion 15/15Checklist OK 2Open Snags 2Total Snags 11Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type, BTS Type, Site Sharing.

Site & Handover Details

Site CodeSYL_X0257ZoneSylhet
HOTO Date2026-09-03DistrictMoulavibazar
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonOmar FarukTakeover PersonSourav
Handover Phone01406394566Takeover Phone01847426870
Inspected Bysourov sarkarSecurity GuardNo
Access Key Handed Over—Site TypeNot Filled
BTS TypeNot Filled
Shared with OperatorNot FilledShared Operator Name—

Generator Information

DG BrandFG WilsonGenset Asset No.No
Capacity (KVA)22TypeCan
Fuel Tank Capacity2000Present RH633
Fuel (no water)223 LFuel (total)223 L
Water Amount— LFuel Amount (word)Two Hundred Twenty Three Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandVolvoBattery Serial27MB0579
Battery AH100Engine SerialN844L2216M5260
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-05-08
Key TypeLocal KeyKey Status β€” BTSAbloy
Key Status β€” DG RoomOpen space
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DG—Faulty/Disconnected Tanks—

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)24
Frequency (Hz)50.2Phase3 Phase
Output24Voltage L1-L2389
Voltage L2-L3380Voltage L3-L1385
Voltage L1-N220Voltage L2-N215
Voltage L3-N215Current Line 18
Current Line 28Current Line 38
Engine BrandPerkins Controller StatusOK
Black Smoke StatusOKDG Battery ChargerOK
ATS Physical & Functional StatusOKDG Automation (VDTC/RVDTC/Rectifier) per BL StandardOK
Fuel Preserved at Safe & Appropriate LocationOKExhaust Fan / Ventilation Sufficient When RunningOK
Sufficient Water in Radiator & BatteryOKDG Radiator ConditionOK
DG Battery ConditionOKDG Runs in Both Auto & Manual ModeOK
GENSET ON Alarm Functioning ProperlyOKLub Oil Status (Level & Colour)OK
DG RH Meter Working ProperlyOKNo Parts Missing (if missing, note in snags below)OK

Snags Found (2)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-013 DG DG - Other Hi temp sensor Faulty — Open —
S-014 DG DG - Other DG Rusty Faulty — Open

Deficiencies & Safety Remarks

DG Major Deficiencies—
Safety Remarks—
General Remarks—

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge

Additional

Additional

Additional

Additional

Additional

Additional

Additional
Omar Faruk
Handed Over By · Dhaly Infratech
01406394566
Date:  
Sourav
Taken Over By · Alliance Computers Limited
01847426870
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (11)

Full-size reference photos for SYL_X0257, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (1)

Photo 4 β€” S-014 β€” DG Rusty

Additional Photos (7)

Photo 5 β€” Additional Photos 1
Photo 6 β€” Additional Photos 2
Photo 7 β€” Additional Photos 3
Photo 8 β€” Additional Photos 4
Photo 9 β€” Additional Photos 5
Photo 10 β€” Additional Photos 6
Photo 11 β€” Additional Photos 7

Download / Print PDFEdit Before Printing