Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0554

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
100%Form Completion 12/15Checklist OK 5Open Snags 5Total Snags 8Photos Attached

Site & Handover Details

Site CodeSYL_X0554ZoneSylhet
HOTO Date2026-09-03DistrictSunamganj
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd. AnwarTakeover PersonMd. Ismail Hossain.
Handover Phone01734713807Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardNo
Access Key Handed OverYesSite TypeGFT
BTS TypeIndoor
Shared with OperatorYesShared Operator NameGrameen Phone

Generator Information

DG BrandPramacGenset Asset No.N/A
Capacity (KVA)22TypeCan
Fuel Tank Capacity1000Present RH2472
Fuel (no water)110 LFuel (total)144 L
Water Amount34 LFuel Amount (word)One Hundred Forty Four Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON Alarm
Battery Brand100Battery SerialP033WECK0045
Battery AH100Engine SerialGN65750U9457745
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-06-21
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)22
Frequency (Hz)52Phase3 Phase
Output400Engine BrandPerkings
Voltage L1-L2400Voltage L2-L3401
Voltage L3-L1398Voltage L1-N231
Voltage L2-N230Voltage L3-N229
Current Line 110Current Line 210
Current Line 30N-G2.21
Controller StatusOKBlack Smoke StatusNOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationNOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)NOKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (5)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-047 DG DG - Other Lube oil level is low Faulty Open
S-048 DG DG - Other Need to overhaling issue because lube oil is leaking from the engine gasket. Faulty Open
S-049 DG DG - Other (unspecified) Faulty The fuel tank is installed in an open area, fuel could be stolen at any time. Open
S-050 DG DG - Other Black smoke is coming out of the silencer pipe. Faulty With the engine turned off Open
S-051 DG DG - Other when engine start Faulty Open

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Anwar
Handed Over By · Dhaly Infratech
01734713807
Date:  
Md. Ismail Hossain.
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (8)

Full-size reference photos for SYL_X0554, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (5)

Photo 4 β€” S-047 β€” Lube oil level is low
Photo 5 β€” S-048 β€” Need to overhaling issue because lube oil is leaking from the engine gasket.
Photo 6 β€” S-049 β€” (unspecified)
Photo 7 β€” S-050 β€” Black smoke is coming out of the silencer pipe.
Photo 8 β€” S-051 β€” when engine start