Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0364

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
73%Form Completion 15/15Checklist OK 0Open Snags 0Total Snags 8Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type, BTS Type, Site Sharing.

Site & Handover Details

Site CodeSYL_X0364ZoneSylhet
HOTO Date2026-09-03DistrictMoulavibazar
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonOmar FarukTakeover PersonSourav
Handover Phone01406394566Takeover Phone01847426870
Inspected Bysourov sarkarSecurity GuardYes
Access Key Handed OverSite TypeNot Filled
BTS TypeNot Filled
Shared with OperatorNot FilledShared Operator Name

Generator Information

DG BrandFG WilsonGenset Asset No.No
Capacity (KVA)30TypeCan
Fuel Tank Capacity2000Present RH146.4
Fuel (no water)394 LFuel (total)394 L
Water Amount00 LFuel Amount (word)Three Hundred Ninety Four Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandVolvoBattery Serial05BB0325
Battery AH100Engine SerialDJ32015
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-07-28
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)23
Frequency (Hz)50.3Phase3 Phase
Output23Voltage L1-L2390
Voltage L2-L3395Voltage L3-L1389
Voltage L1-N210Voltage L2-N205
Voltage L3-N212Current Line 18
Current Line 27Current Line 38
Engine BrandPerkins Controller StatusOK
Black Smoke StatusOKDG Battery ChargerOK
ATS Physical & Functional StatusOKDG Automation (VDTC/RVDTC/Rectifier) per BL StandardOK
Fuel Preserved at Safe & Appropriate LocationOKExhaust Fan / Ventilation Sufficient When RunningOK
Sufficient Water in Radiator & BatteryOKDG Radiator ConditionOK
DG Battery ConditionOKDG Runs in Both Auto & Manual ModeOK
GENSET ON Alarm Functioning ProperlyOKLub Oil Status (Level & Colour)OK
DG RH Meter Working ProperlyOKNo Parts Missing (if missing, note in snags below)OK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge

Additional

Additional

Additional

Additional

Additional
Omar Faruk
Handed Over By · Dhaly Infratech
01406394566
Date:  
Sourav
Taken Over By · Alliance Computers Limited
01847426870
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (8)

Full-size reference photos for SYL_X0364, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Additional Photos (5)

Photo 4 β€” Site Context 1
Photo 5 β€” Site Context 2
Photo 6 β€” Site Context 3
Photo 7 β€” Site Context 4
Photo 8 β€” Site Context 5

Download / Print PDFEdit Before Printing