Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0156

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
100%Form Completion 14/15Checklist OK 3Open Snags 3Total Snags 6Photos Attached

Site & Handover Details

Site CodeSYL_X0156ZoneSylhet
HOTO Date2026-09-02DistrictSunamganj
Handover OrgDhaly Infratech Ltd.Takeover OrgAlliance Computers Limited.
Handover PersonMD. Eidris Ali.Takeover PersonMD. Ismail Hossain.
Handover Phone01750537433Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGFT
BTS TypeOutdoor
Shared with OperatorNoShared Operator NameN/A

Generator Information

DG BrandTempestGenset Asset No.10030010KUE
Capacity (KVA)20TypeCan
Fuel Tank Capacity800Present RH2869.14
Fuel (no water)245 LFuel (total)245 L
Water Amount— LFuel Amount (word)Two Hundred Forty Five Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033WIDE0634
Battery AH100Engine SerialJV51790U983071B
ATS BrandLOCALATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-04-26
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)45
Frequency (Hz)52.2Phase3 Phase
Output376Engine BrandpERKINGS
Voltage L1-L2376Voltage L2-L3376
Voltage L3-L1378Voltage L1-N217
Voltage L2-N217Voltage L3-N217
Current Line 115Current Line 215
Current Line 315N-G1.35
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionNOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (3)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-020 DG DG - Other Dg controller display not clean, Nothing on the display is visible Faulty Open
S-021 DG DG - Other Radiator ful block dust Faulty Open
S-022 DG DG - Other DG fan belt loose. Faulty Open

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
MD. Eidris Ali.
Handed Over By · Dhaly Infratech Ltd.
01750537433
Date:  
MD. Ismail Hossain.
Taken Over By · Alliance Computers Limited.
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (6)

Full-size reference photos for SYL_X0156, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (3)

Photo 4 β€” S-020 β€” Dg controller display not clean, Nothing on the display is visible
Photo 5 β€” S-021 β€” Radiator ful block dust
Photo 6 β€” S-022 β€” DG fan belt loose.