Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0103

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
73%Form Completion 15/15Checklist OK 2Open Snags 2Total Snags 14Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type, BTS Type, Site Sharing.

Site & Handover Details

Site CodeSYL_X0103ZoneSylhet
HOTO Date2026-09-02DistrictMoulavibazar
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonSayedTakeover PersonSourav sarkar
Handover Phone017163327Takeover Phone01847426870
Inspected Bysourov sarkarSecurity Guard
Access Key Handed OverSite TypeNot Filled
BTS TypeNot Filled
Shared with OperatorNot FilledShared Operator Name

Generator Information

DG BrandGhadderGenset Asset No.
Capacity (KVA)20TypeCan
Fuel Tank Capacity2000Present RH7873
Fuel (no water)354 LFuel (total)354 L
Water Amount— LFuel Amount (word)Three Hundred Fifty Four Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandSparkBattery Serial3J06AL11015303
Battery AH80Engine SerialN8431496N52001
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-06-18
Key TypeMaster Key - AbloyKey Status β€” BTSAbloy
Key Status β€” DG RoomAbloy
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Engine BrandPerkins Controller StatusOK
Black Smoke StatusOKDG Battery ChargerOK
ATS Physical & Functional StatusOKDG Automation (VDTC/RVDTC/Rectifier) per BL StandardOK
Fuel Preserved at Safe & Appropriate LocationOKExhaust Fan / Ventilation Sufficient When RunningOK
Sufficient Water in Radiator & BatteryOKDG Radiator ConditionOK
DG Battery ConditionOKDG Runs in Both Auto & Manual ModeOK
GENSET ON Alarm Functioning ProperlyOKLub Oil Status (Level & Colour)OK
DG RH Meter Working ProperlyOKNo Parts Missing (if missing, note in snags below)OK

Snags Found (2)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-003 DG DG - Other Fuel pipe hard Faulty Open
S-004 DG DG - Other Need to fuel tank lock system,& pipe protection Faulty Open

Deficiencies & Safety Remarks

DG Major DeficienciesHi temp sensor NOK
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional
Sayed
Handed Over By · Dhaly Infratech
017163327
Date:  
Sourav sarkar
Taken Over By · Alliance Computers Limited
01847426870
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (14)

Full-size reference photos for SYL_X0103, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (1)

Photo 4 β€” S-004 β€” Need to fuel tank lock system,& pipe protection

Additional Photos (10)

Photo 5 β€” Site Context 1
Photo 6 β€” Site Context 2
Photo 7 β€” Site Context 3
Photo 8 β€” Site Context 4
Photo 9 β€” Site Context 5
Photo 10 β€” Site Context 6
Photo 11 β€” Site Context 7
Photo 12 β€” Site Context 8
Photo 13 β€” Site Context 9
Photo 14 β€” Site Context 10

Download / Print PDFEdit Before Printing