Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0089

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
100%Form Completion 14/15Checklist OK 1Open Snags 1Total Snags 8Photos Attached

Site & Handover Details

Site CodeSYL_X0089ZoneSylhet
HOTO Date2026-09-01DistrictSunamganj
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd. AnwarTakeover PersonMd. Ismail Hossain
Handover Phone01734713807Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGFT
BTS TypeOutdoor
Shared with OperatorNoShared Operator NameN/A

Generator Information

DG BrandTempestGenset Asset No.N/A
Capacity (KVA)20TypeCan
Fuel Tank Capacity2000Present RH2241
Fuel (no water)104 LFuel (total)104 L
Water Amount— LFuel Amount (word)One hundred four litter
DG Site TypeRemoteDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialP033XEBD0616
Battery AH100Engine SerialGN66044U
ATS BrandLocalATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-04-30
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)34
Frequency (Hz)51Phase3 Phase
Output410Engine BrandParkings
Voltage L1-L2410Voltage L2-L3410
Voltage L3-L1409Voltage L1-N235
Voltage L2-N235Voltage L3-N234
Current Line 111Current Line 212
Current Line 311N-G0.047
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)NOKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (1)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-008 DG DG - Other Over Run Faulty Open

Deficiencies & Safety Remarks

DG Major DeficienciesNeed to servicing
Safety RemarksNeed to servicing
General RemarksNeed to servicing

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge

Additional

Additional

Additional

Additional
Md. Anwar
Handed Over By · Dhaly Infratech
01734713807
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (8)

Full-size reference photos for SYL_X0089, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (1)

Photo 4 β€” S-008 β€” Over Run

Additional Photos (4)

Photo 5 β€” Site Context 1
Photo 6 β€” Site Context 2
Photo 7 β€” Site Context 3
Photo 8 β€” Site Context 4

Download / Print PDFEdit Before Printing