Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0077

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
100%Form Completion 20/20Checklist OK 0Open Snags 0Total Snags 4Photos Attached

Site & Handover Details

Site CodeSYL_X0077ZoneSylhet
HOTO Date2026-09-01DistrictMoulavibazar
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonOmar FarukTakeover PersonSourav sarkar
Handover Phone01406394566Takeover Phone0184742670
Inspected Bysourov sarkarSecurity GuardYes
Access Key Handed OverSite TypeGFT
BTS TypeIndoor
Shared with OperatorNoShared Operator Name

Generator Information

DG BrandVisaGenset Asset No.No
Capacity (KVA)30TypeCan
Fuel Tank Capacity2000Present RH629.2
Fuel (no water)— LFuel (total)327 L
Water Amount— LFuel Amount (word)Three Hundred Twenty Seven Liters
DG Site TypeDG Locked After Fueling
DG Present StatusOK Genset ON AlarmOK
Battery BrandHamkoBattery SerialPO33WJBK0524
Battery AH100Engine SerialDJ51279
ATS BrandBanglaATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-06-28
Key TypeMaster Key - AbloyKey Status β€” BTSSolex
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesPhase3 Phase
Voltage L1-L2390Voltage L2-L3400
Voltage L3-L1395Voltage L1-N200
Voltage L2-N210Voltage L3-N220
Current Line 18Current Line 28
Current Line 39Engine BrandPerkn
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OKMains Fail AlarmOK
DC Low AlarmOKDoor Open AlarmOK
DG Run AlarmOKDG Failure AlarmOK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major DeficienciesDG Fuel pipe hard need to change Need to DG Radiator servicing DG Room light faulty Need to Fuel tank locking system
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge

Additional
Omar Faruk
Handed Over By · Dhaly Infratech
01406394566
Date:  
Sourav sarkar
Taken Over By · Alliance Computers Limited
0184742670
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (4)

Full-size reference photos for SYL_X0077, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Additional Photos (1)

Photo 4 β€” Site Context 1