Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0069

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 25-Oct-2026 20:26 BD time
91%Form Completion 8/15Checklist OK 6Open Snags 6Total Snags 35Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type.

Site & Handover Details

Site CodeSYL_X0069ZoneSylhet
HOTO Date2026-09-01DistrictSunamganj
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd AnwarTakeover PersonMd. Ismail Hossain
Handover Phone01734713807Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeNot Filled
BTS TypeIndoor
Shared with OperatorNoShared Operator Name—

Generator Information

DG BrandSDMOGenset Asset No.N/A
Capacity (KVA)30TypeCan
Fuel Tank Capacity2000Present RH2952.9
Fuel (no water)55 LFuel (total)114 L
Water Amount59 LFuel Amount (word)Fifty five litter
DG Site TypeRemoteDG Locked After FuelingYes
DG Present StatusNOK Genset ON AlarmNOK
Battery BrandHamkoBattery SerialP033XFDI0753
Battery AH100Engine Serial3029DF120
ATS BrandJRCATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-05-29
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomLocal
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DG0Faulty/Disconnected Tanks0

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)0
Frequency (Hz)0Phase3 Phase
Output0Engine BrandJohn Deere
Voltage L1-L20Voltage L2-L30
Voltage L3-L10Voltage L1-N0
Voltage L2-N0Voltage L3-N0
Current Line 10Current Line 20
Current Line 30N-G0
Controller StatusOKBlack Smoke StatusNOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardNOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryNOK
DG Radiator ConditionNOKDG Battery ConditionNOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyNOK
Lub Oil Status (Level & Colour)NOKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (6)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-136 General — DG (generator) Faulty DG marked 'Faulty' under Generator status during handover; all electrical readings (load current, frequency, voltage levels, output) recorded as 0. Remarks state 'DG Permanent Faulty'. (from paper HOTO checklist PDF, transcribed 2026-09-16) Open —
S-137 General — Black smoke status Faulty Marked NOK (from paper HOTO checklist PDF, transcribed 2026-09-16) Open —
S-138 General — Sufficient water in radiator/battery Faulty Marked NOK (from paper HOTO checklist PDF, transcribed 2026-09-16) Open —
S-139 General — DG radiator condition Faulty Marked NOK (from paper HOTO checklist PDF, transcribed 2026-09-16) Open —
S-140 General — DG running in Auto/Manual mode Faulty Marked NOK (from paper HOTO checklist PDF, transcribed 2026-09-16) Open —
S-141 General — Lub Oil Status Faulty Marked NOK (from paper HOTO checklist PDF, transcribed 2026-09-16) Open —

Deficiencies & Safety Remarks

DG Major DeficienciesDG permanent faulty
Safety RemarksDG permanent faulty
General RemarksDG permanent faulty | PDF checklist notes: This DG is recorded as permanently faulty (all electrical readings zero, multiple checklist items NOK: black smoke, radiator water, radiator condition, auto/manual running, lub oil). GENSET ON alarm row is annotated 'Not check' (not evaluated) rather than OK/NOK. Handover status row shows check marks near BOTH 'Completed' and 'Not Completed' boxes - genuinely ambiguous on the form; given the DG is noted permanently faulty, 'Not Completed' is more plausible but this should be verified by a human. RVDT annotation appears next to the DG automation row (context unclear).

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional

Additional
Md Anwar
Handed Over By · Dhaly Infratech
01734713807
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (35)

Full-size reference photos for SYL_X0069, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Additional Photos (32)

Photo 4 β€” Additional Photos 1
Photo 5 β€” Additional Photos 2
Photo 6 β€” Additional Photos 3
Photo 7 β€” Additional Photos 4
Photo 8 β€” Additional Photos 5
Photo 9 β€” Additional Photos 6
Photo 10 β€” Additional Photos 7
Photo 11 β€” Additional Photos 8
Photo 12 β€” Additional Photos 9
Photo 13 β€” Additional Photos 10
Photo 14 β€” Additional Photos 11
Photo 15 β€” Additional Photos 12
Photo 16 β€” Additional Photos 13
Photo 17 β€” Additional Photos 14
Photo 18 β€” Additional Photos 15
Photo 19 β€” Additional Photos 16
Photo 20 β€” Additional Photos 17
Photo 21 β€” Additional Photos 18
Photo 22 β€” Additional Photos 19
Photo 23 β€” Additional Photos 20
Photo 24 β€” Additional Photos 21
Photo 25 β€” Additional Photos 22
Photo 26 β€” Additional Photos 23
Photo 27 β€” Additional Photos 24
Photo 28 β€” Additional Photos 25
Photo 29 β€” Additional Photos 26
Photo 30 β€” Additional Photos 27
Photo 31 β€” Additional Photos 28
Photo 32 β€” Additional Photos 29
Photo 33 β€” Additional Photos 30
Photo 34 β€” Additional Photos 31
Photo 35 β€” Additional Photos 32

Download / Print PDFEdit Before Printing