Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_X0067

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
73%Form Completion 14/15Checklist OK 0Open Snags 0Total Snags 3Photos Attached
Incomplete: the following expected fields were left blank in this submission β€” Site Type, BTS Type, Site Sharing.

Site & Handover Details

Site CodeSYL_X0067ZoneSylhet
HOTO Date2026-08-31DistrictMoulavibazar
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonOmar FarukTakeover PersonSourav sarkar
Handover Phone01406394566Takeover Phone01847426870
Inspected Bysourov sarkarSecurity GuardYes
Access Key Handed OverSite TypeNot Filled
BTS TypeNot Filled
Shared with OperatorNot FilledShared Operator Name

Generator Information

DG BrandFG WilsonGenset Asset No.No
Capacity (KVA)30TypeCan
Fuel Tank Capacity2000Present RH
Fuel (no water)372 LFuel (total)372 L
Water Amount— LFuel Amount (word)Three Hundred Seventy Two Liters
DG Site TypeStandardDG Locked After FuelingYes
DG Present StatusOK Genset ON AlarmOK
Battery BrandVolvoBattery Serial25JB0612
Battery AH100Engine SerialDJ320155009844C
ATS BrandBanglaATS ModeAuto
RH Meter TypeDigital from controllerLast Service Date2026-05-21
Key TypeKey Status β€” BTSAbloy
Key Status β€” DG RoomSolex
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)66
Frequency (Hz)50.5Phase3 Phase
Output66Voltage L1-L2390
Voltage L2-L3400Voltage L3-L1390
Voltage L1-N220Voltage L2-N222
Voltage L3-N218Current Line 118
Current Line 229Current Line 319
Engine BrandPerkins Controller StatusOK
Black Smoke StatusOKDG Battery ChargerOK
ATS Physical & Functional StatusOKDG Automation (VDTC/RVDTC/Rectifier) per BL StandardOK
Fuel Preserved at Safe & Appropriate LocationOKExhaust Fan / Ventilation Sufficient When RunningOK
Sufficient Water in Radiator & BatteryOKDG Radiator ConditionOK
DG Battery ConditionOKDG Runs in Both Auto & Manual ModeOK
GENSET ON Alarm Functioning ProperlyOKLub Oil Status (Level & Colour)NOK
DG RH Meter Working ProperlyOKNo Parts Missing (if missing, note in snags below)OK

Snags Found (0)

No snags logged for this visit.

Deficiencies & Safety Remarks

DG Major DeficienciesLub oil shortage ATS Door cobja broken DG Front side canopy missing DG Base not fixed AC power cable twist DG room light not found
Safety Remarks
General Remarks

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Omar Faruk
Handed Over By · Dhaly Infratech
01406394566
Date:  
Sourav sarkar
Taken Over By · Alliance Computers Limited
01847426870