Banglalink Alliance Computers Limited

Site HOTO Report β€” SYL_G0420

Project Tiger · Dhaly Infratech → Alliance Computers Limited · Generated 07-Sep-2026 19:48 BD time
100%Form Completion 14/15Checklist OK 1Open Snags 1Total Snags 4Photos Attached

Site & Handover Details

Site CodeSYL_G0420ZoneSylhet
HOTO Date2026-09-01DistrictSunamganj
Handover OrgDhaly InfratechTakeover OrgAlliance Computers Limited
Handover PersonMd. AnwarTakeover PersonMd. Ismail Hossain
Handover Phone01734713807Takeover Phone01847426858
Inspected ByIsmail SirajiSecurity GuardYes
Access Key Handed OverYesSite TypeGF-RT
BTS TypeIndoor
Shared with OperatorYesShared Operator NameGrameen Phone

Generator Information

DG BrandTempestGenset Asset No.N/A
Capacity (KVA)22TypeCan
Fuel Tank Capacity2000Present RH3498.4
Fuel (no water)178 LFuel (total)297 L
Water Amount119 LFuel Amount (word)One Hundred Seventy Eight Li
DG Site TypeRemoteDG Locked After Fueling
DG Present StatusOK Genset ON AlarmOK
Battery BrandVolvoBattery Serial3A15VOI12787308
Battery AHEngine SerialGNG65732U939425V
ATS BrandATS Mode
RH Meter TypeLast Service Date
Key TypeLocal KeyKey Status β€” BTSLocal
Key Status β€” DG RoomOpen
Active DG1Connected Fuel Tanks1
Faulty/Disconnected DGFaulty/Disconnected Tanks

Connected Generator Checklist & Readings

ItemValueItemValue
Earth Connection OKYesLoad Current (A)24
Frequency (Hz)49Phase3 Phase
Output400Engine BrandPerkings
Voltage L1-L2398Voltage L2-L3398
Voltage L3-L1400Voltage L1-N229
Voltage L2-N229Voltage L3-N230
Current Line 112Current Line 213
Current Line 30N-G.057
Controller StatusOKBlack Smoke StatusOK
DG Battery ChargerOKATS Physical & Functional StatusOK
DG Automation (VDTC/RVDTC/Rectifier) per BL StandardOKFuel Preserved at Safe & Appropriate LocationOK
Exhaust Fan / Ventilation Sufficient When RunningOKSufficient Water in Radiator & BatteryOK
DG Radiator ConditionNOKDG Battery ConditionOK
DG Runs in Both Auto & Manual ModeOKGENSET ON Alarm Functioning ProperlyOK
Lub Oil Status (Level & Colour)OKDG RH Meter Working ProperlyOK
No Parts Missing (if missing, note in snags below)OK

Snags Found (1)

Snag #SystemCategoryComponentStatusObservationsActionPhoto
S-009 DG DG - Other Radiator fully block dust Faulty Open

Deficiencies & Safety Remarks

DG Major Deficiencies
Safety Remarks
General Remarks1) Hedgasket problem 2) Rediotor jum/ not cilin

Site Photos


Site / Nameplate

DG RH / Meter

Fuel Gauge
Md. Anwar
Handed Over By · Dhaly Infratech
01734713807
Date:  
Md. Ismail Hossain
Taken Over By · Alliance Computers Limited
01847426858
Date:  
 
BL Concern · Name / Signature
 
Date:  

Appendix β€” Photo Evidence (4)

Full-size reference photos for SYL_G0420, grouped by type and numbered for cross-reference against the tables above.

Required Site Photos (3)

Photo 1 β€” Site / Nameplate
Photo 2 β€” DG RH / Meter
Photo 3 β€” Fuel Gauge

Snag Evidence Photos (1)

Photo 4 β€” S-009 β€” Radiator fully block dust

Download / Print PDFEdit Before Printing